Fire-Resistance Rated Assemblies
Your Guide to Code-Compliant Construction
Fire-resistance rated assemblies play a critical role in protecting occupants, slowing fire spread, and helping builders meet code requirements. Learn when fire-resistance rated assemblies are required, how they are tested, and how ZIP System® and EXACOR® products can be incorporated into tested assemblies.
Whether you're navigating code requirements, evaluating assembly options, or looking for supporting documentation, our team can help.
Understanding Fire-Resistance Rated Solutions
What you need to know about fire-resistance rated construction
Fire-resistance rated construction is designed to help contain fire, maintain structural stability, and provide occupants additional time to evacuate. Fire-resistance rated assemblies are tested systems made up of multiple components working together to achieve a specific fire-resistance rating. Fire-resistance rated assemblies help slow the spread of fire, protect adjacent structures, and support code compliance across a variety of residential and commercial applications. As building codes continue to evolve and wildfire concerns grow, fire-resistance rated assemblies have become increasingly important in residential, multifamily, and commercial construction.
When are fire-resistance rated assemblies required?
Learn MoreWhat determines the core fire-resistance rated code requirements?
Learn MoreWhich fire-resistance rated solutions does Huber offer?
Learn MoreWhich solution is right for your project?
Learn MoreCommon Applications
When Are Fire-Resistance Rated Assemblies Required?
Requirements vary by project type, location and local building code, but fire-resistance rated assemblies are commonly required in:
- Exterior walls
- Townhomes
- Multifamily buildings
- Condominiums
- Commercial construction
- Zero lot-line construction
- Buildings with limited fire separation distance
- Wildland-urban interface (WUI) zones
Always verify project-specific requirements with your local authority having jurisdiction.
Navigating Fire-Resistance Rated Construction
Understanding fire-resistance rated code requirements
Fire-resistance rated requirements are influenced by several factors, including:
- International Building Code (IBC)
- International Residential Code (IRC)
- Local amendments
- Construction type
- Occupancy classification
- Fire separation distance (FSD)
- WUI regulations, where applicable
Which Fire-Resistance Rated Assemblies does Huber offer?
EXACOR® Products
EXACOR MgO panels provide fire-resistant performance and may be incorporated into multiple tested assemblies for residential, multifamily and commercial applications[1].
- Fire-resistant MgO technology
- 1-hour assemblies
- 2-hour assemblies
- Multifamily applications[2]
- ASTM E119 testing
- Fire and sound performance
ZIP System® Sheathing
ZIP System sheathing can be incorporated into multiple fire-resistance rated wall assemblies[1], helping builders achieve code compliance while maintaining the performance benefits of an integrated building enclosure.
- Proprietary assemblies (ESL-1691)
- Substitution method
- Addition method
Fire-resistance rated assembly identification tool[3]
Filter by product, application, fire-resistance rating, construction type and other criteria to find tested assemblies that may fit fit your project requirements.
| Product | Application | Construction Type | Fire-Resistance Rating (Exterior/Interior) | Assembly ID | Assembly Name | Rated From | Cladding Type | Framing Size | Wall Framing Type | Source Document | Floor/Ceiling Framing Type |
|---|---|---|---|---|---|---|---|---|---|---|---|
| ZIP System R-Sheathing | Wall | Type V | N/A/1-hr | ZIPR-001 | UL V302 | Rated from interior only | Unspecified/not listed | Minimum nominal 2 x 4 in. | Wood | ZIP R Handbook | N/A |
| ZIP System R-Sheathing | Wall | Type V | N/A/1-hr | ZIPR-002 | UL V303 | Rated from interior only | Unspecified/not listed | Minimum nominal 2 x 4 in. | Wood | ZIP R Handbook | N/A |
| ZIP System R-Sheathing | Wall | Type V | N/A/1-hr | ZIPR-003 | UL V318 | Rated from interior only | Unspecified/not listed | Minimum nominal 2 x 4 in. | Wood | ZIP R Handbook | N/A |
| ZIP System R-Sheathing | Wall | Type V | N/A/1-hr | ZIPR-004 | UL U355 | Rated from interior only | Unspecified/not listed | Minimum nominal 2 x 6 in. | Wood | ZIP R Handbook | N/A |
| ZIP System R-Sheathing | Wall | Type V | 1-hr/1-hr | ZIPR-005 | UL U364 | Rated from the interior and exterior | Vinyl | Minimum nominal 2 x 4 in. | Wood | ZIP R Handbook | N/A |
| ZIP System R-Sheathing | Wall | Type V | 1-hr/1-hr | ZIPR-005 | UL U364 | Rated from the interior and exterior | Brick | Minimum nominal 2 x 4 in. | Wood | ZIP R Handbook | N/A |
| ZIP System R-Sheathing | Wall | Type V | 1-hr/1-hr | ZIPR-005 | UL U364 | Rated from the interior and exterior | Stucco | Minimum nominal 2 x 4 in. | Wood | ZIP R Handbook | N/A |
| ZIP System R-Sheathing | Wall | Type V | 1-hr/1-hr | ZIPR-005 | UL U364 | Rated from the interior and exterior | APA exterior-rated plywood | Minimum nominal 2 x 4 in. | Wood | ZIP R Handbook | N/A |
| ZIP System R-Sheathing | Wall | Type V | 1-hr/1-hr | ZIPR-005 | UL U364 | Rated from the interior and exterior | Engineered wood-based | Minimum nominal 2 x 4 in. | Wood | ZIP R Handbook | N/A |
| ZIP System Sheathing | Wall | Type V | 1-hr/1-hr | ZIP-001 | ESL-1691 | Rated from the interior and exterior | APA exterior-rated plywood | Minimum nominal 2 x 6 in. | Wood | ZIP Fire Handbook | N/A |
| ZIP System Sheathing | Wall | Type V | 1-hr/1-hr | ZIP-002 | ESL-1691 | Rated from the interior and exterior | Fiber-cement | Minimum nominal 2 x 6 in. | Wood | ZIP Fire Handbook | N/A |
| ZIP System Sheathing | Wall | Type V | 1-hr/1-hr | ZIP-003 | ESL-1691 | Rated from the interior and exterior | Stucco | Minimum nominal 2 x 6 in. | Wood | ZIP Fire Handbook | N/A |
| ZIP System Sheathing | Wall | Type V | 1-hr/1-hr | ZIP-004 | ESL-1691 | Rated from the interior and exterior | Brick | Minimum nominal 2 x 6 in. | Wood | ZIP Fire Handbook | N/A |
| ZIP System Sheathing | Wall | Type V | 1-hr/1-hr | ZIP-005 | RI/MFF 60-04 | Rated from the interior and exterior | Stucco | Minimum nominal 2 x 4 in. | Wood | ZIP Fire Handbook | N/A |
| ZIP System Sheathing | Wall | Type V | N/A/1-hr | ZIP-006 | UL U356 | Rated from interior only | Vinyl | Minimum nominal 2 x 4 in. | Wood | ZIP Fire Handbook | N/A |
| ZIP System Sheathing | Wall | Type V | N/A/1-hr | ZIP-007 | UL U356 | Rated from interior only | Engineered wood-based | Minimum nominal 2 x 4 in. | Wood | ZIP Fire Handbook | N/A |
| ZIP System Sheathing | Wall | Type V | N/A/1-hr | ZIP-008 | UL U356 | Rated from interior only | Stucco | Minimum nominal 2 x 4 in. | Wood | ZIP Fire Handbook | N/A |
| ZIP System Sheathing | Wall | Type V | N/A/1-hr | ZIP-009 | UL U356 | Rated from interior only | Brick | Minimum nominal 2 x 4 in. | Wood | ZIP Fire Handbook | N/A |
| ZIP System Sheathing | Wall | Type V | N/A/1-hr | ZIP-010 | UL U356 | Rated from interior only | Fiber-cement | Minimum nominal 2 x 4 in. | Wood | ZIP Fire Handbook | N/A |
| ZIP System Sheathing | Wall | Type V | 1-hr/1-hr | ZIP-011 | UL U305 | Rated from the interior and exterior | Unspecified/not listed | Minimum nominal 2 x 4 in. | Wood | ZIP Fire Handbook | N/A |
| EXACOR Sheathing | Wall | Type III | 2-hr/2-hr | EXW-001 | MOS-1290-03 | Rated from the interior and exterior | Unspecified/not listed | Minimum nominal 2 x 6 in. | Wood | EXACOR Handbook | N/A |
| EXACOR Sheathing | Wall | Type III | 1-hr/1-hr | EXW-002 | MOS-1290-04 | Rated from the interior and exterior | Unspecified/not listed | Minimum nominal 2 x 4 in. | Wood | EXACOR Handbook | N/A |
| EXACOR Sheathing | Wall | Type III | 1-hr/2-hr | EXW-003 | MOS-1290-06 | Rated from the interior and exterior | Engineered wood-based | Minimum nominal 2 x 4 in. | Wood | EXACOR Handbook | N/A |
| EXACOR Sheathing | Wall | Type III | 1-hr/2-hr | EXW-004 | MOS-1290-06 | Rated from the interior and exterior | Fiber-cement | Minimum nominal 2 x 4 in. | Wood | EXACOR Handbook | N/A |
| EXACOR Sheathing | Wall | Type III | 1-hr/2-hr | EXW-005 | MOS-1290-06 | Rated from the interior and exterior | Stucco | Minimum nominal 2 x 4 in. | Wood | EXACOR Handbook | N/A |
| EXACOR Sheathing | Wall | Type III | 1-hr/2-hr | EXW-006 | MOS-1290-06 | Rated from the interior and exterior | Brick | Minimum nominal 2 x 4 in. | Wood | EXACOR Handbook | N/A |
| EXACOR Sheathing | Townhome Separation | Type III | 2-hr/2-hr | EXW-007 | MOS-1290-07A | Rated from the interior and exterior | Unspecified/not listed | Minimum nominal 2 x 4 in. | Wood | EXACOR Handbook | N/A |
| EXACOR Sheathing | Townhome Separation | Type III | 2-hr/2-hr | EXW-008 | MOS-1290-07B | Rated from the interior and exterior | Unspecified/not listed | Minimum nominal 2 x 4 in. | Wood | EXACOR Handbook | N/A |
| EXACOR Sheathing | Townhome Separation | Type III | 2-hr/2-hr | EXW-009 | MOS-1290-08 | Rated from the interior and exterior | Unspecified/not listed | Minimum nominal 2 x 4 in. | Wood | EXACOR Handbook | N/A |
| EXACOR Sheathing | Wall | Type III | NFPA 285 Compliant | EXW-010 | MOS-1290-05 | N/A | Other | Minimum nominal 2 x 4 in. | Wood | EXACOR Handbook | N/A |
| EXACOR Sheathing | Wall | Type III | NFPA 285 Compliant | EXW-010 | MOS-1290-05 | N/A | Fiber-cement | Minimum nominal 2 x 4 in. | Wood | EXACOR Handbook | N/A |
| EXACOR Sheathing | Wall | Type III | NFPA 285 Compliant | EXW-010 | MOS-1290-05 | N/A | Brick | Minimum nominal 2 x 4 in. | Wood | EXACOR Handbook | N/A |
| EXACOR Sheathing | Wall | Type III | NFPA 285 Compliant | EXW-010 | MOS-1290-05 | N/A | Stucco | Minimum nominal 2 x 4 in. | Wood | EXACOR Handbook | N/A |
| EXACOR Underlayment | Floor | Type V | 1-hr/1-hr | EXF-001 | UL L528 | N/A | N/A | N/A | N/A | EXACOR Handbook | Wood Truss |
| EXACOR Underlayment | Floor | Type V | 1-hr/1-hr | EXF-002 | UL L546 | N/A | N/A | N/A | N/A | EXACOR Handbook | Wood Truss |
| EXACOR Underlayment | Floor | Type V | 2-hr/2-hr | EXF-003 | UL M500 | N/A | N/A | N/A | N/A | EXACOR Handbook | Wood Truss |
| EXACOR Underlayment | Floor | Type V | 1-hr/1-hr | EXF-004 | UL L570 | N/A | N/A | N/A | N/A | EXACOR Handbook | Wood I-Joist |
| EXACOR Underlayment | Floor | Type V | 1-hr/1-hr | EXF-005 | UL L602 | N/A | N/A | N/A | N/A | EXACOR Handbook | Wood I-Joist |
| EXACOR Underlayment | Floor | Type V | 1-hr/1-hr | EXF-006 | UL L502 | N/A | N/A | N/A | N/A | EXACOR Handbook | 2x10 Joist |
| EXACOR Underlayment | Floor | Type V | 1-hr/1-hr | EXF-007 | UL L501 | N/A | N/A | N/A | N/A | EXACOR Handbook | 2x10 Joist |
| EXACOR Underlayment | Floor | Type V | 2-hr/2-hr | EXF-008 | UL L511 | N/A | N/A | N/A | N/A | EXACOR Handbook | 2x10 Joist |
| EXACOR Underlayment | Floor | Type V | 1-hr/1-hr | EXF-009 | UL L525 | N/A | N/A | N/A | N/A | EXACOR Handbook | 2x10 Joist |
No assemblies match the selected filters.
Select a filter above to view matching assemblies.
Technical Resources
ESR Reports
(EXACOR)
View Reports
ESR Reports
(ZIP System)
View Reports
ICC-ES Listing Report
(EXACOR)
View Report
ICC-ES Listing Report
(ZIP System)
View Report
Installation Instructions
(EXACOR)
View Guides
Installation Instructions
(ZIP System)
View Guides
Sound and Fire Assemblies
(EXACOR)
View Handbook
Fire-Rated – Sheathing Handbook
(ZIP System)
View Handbook
Fire-Rated – R-Sheathing Handbook
(ZIP System)
View Handbook
Huber Fire-Rated Sell Sheet
(EXACOR & ZIP System)
View Sell Sheet
Need help finding a fire-resistance rated assembly?
Whether you're navigating code requirements, evaluating assembly options or looking for supporting documentation, our technical team can help.