Real-time occupancy-aware air conditioning control for auditoriums, powered by YOLOv8 computer vision, Arduino Uno edge processing, and explainable AI decision-making.
- Project Overview
- System Architecture
- Hardware Components
- Software Modules
- Dashboard Parameters — Complete Reference
- Equations & Mathematical Models
- State Machine & Decision Engine
- Data Flow & Interlinking
- Dual-Zone AC Optimization
- Setup & Installation
- Running the System
- API Endpoints
- Project Structure
- Troubleshooting
AeroSense AI solves a fundamental problem in building HVAC management: conventional air conditioning systems cool rooms at a fixed rate regardless of how many people are present. This wastes enormous amounts of energy — especially in auditoriums and conference halls that cycle between empty and fully occupied states.
- Detects people using a YOLOv8n neural network running on a webcam feed
- Tracks individuals across frames using centroid-based multi-object tracking
- Classifies room state (EMPTY → IDLE → OCCUPIED → BUSY → HIGH_LOAD → COOLING_BOOST) using a hysteresis-protected state machine
- Optimizes dual-zone AC units — independently controlling two air conditioners based on which zone has more people
- Commands physical hardware via Arduino Uno (IR blaster for Midea AC, relay control, LED indicators)
- Displays a real-time dashboard with live video, metrics, thermal models, charts, and an explainable AI engine
Unlike simple on/off timer systems, AeroSense uses temporal intelligence — it considers:
- How many people are present (occupancy count)
- How fast they are moving (activity level from centroid tracking)
- Whether there was a sudden influx (rapid entry detection)
- Hysteresis debouncing to prevent HVAC mode oscillation
┌─────────────────────────────────────────────────────────────────┐
│ VISION PIPELINE │
│ Webcam (Logitech C270) │
│ │ │
│ ▼ │
│ YOLOv8n ONNX Detector ──▶ Centroid Tracker ──▶ Speeds │
│ (person bounding boxes) (persistent IDs) (px/frame) │
└────────────────────────────┬────────────────────────────────────┘
│
▼
┌─────────────────────────────────────────────────────────────────┐
│ DECISION ENGINE │
│ │
│ Zone Assignment ──▶ Dual-AC Optimizer ──▶ AC Commands │
│ (left/right split) (per-zone BTU calc) (temp, fan, on/off) │
│ │
│ State Machine ──▶ HVAC Mode (0-4) ──▶ Comfort Score │
│ (temporal debounce) (ECO→BOOST) (50-100%) │
│ │
│ Thermal Model ──▶ Cooling Load (TR) ──▶ Plant Loading (%) │
│ (BTU calculation) (tons required) (used vs installed) │
└────────────────────────────┬────────────────────────────────────┘
│
┌──────────────┼──────────────┐
▼ ▼ ▼
┌──────────────────┐ ┌────────────┐ ┌────────────────┐
│ Arduino Uno Q │ │ Secondary │ │ Web Dashboard │
│ (Main MCU) │ │ AC via │ │ (FastAPI + │
│ - Relay │ │ Wi-Fi UDP │ │ WebSocket) │
│ - LEDs │ │ IR Blaster│ │ - Live Video │
│ - Serial 115200 │ │ │ │ - Metrics │
└──────────────────┘ └────────────┘ └────────────────┘
| Component | Role | Connection |
|---|---|---|
| Logitech C270 Webcam | Person detection camera | USB to host PC |
| Arduino Uno Q (Main) | Edge controller: relay, LEDs | USB Serial (115200 baud) |
| Arduino (Secondary) | IR blaster for Midea AC unit 2 | Wi-Fi UDP on port 8888 |
| 3-Color LED Array | Visual HVAC mode indicator (Green/Yellow/Blue) | GPIO pins 2, 3, 4 |
| 5V Relay Module | AC compressor simulation / control | GPIO pin 5 |
| IR Transmitter LED | Sends Midea AC protocol codes | Digital Pin 3 (Secondary) |
| IR Receiver (TSOP) | Reads remote control codes | Digital Pin 9 (Secondary) |
| File | Purpose |
|---|---|
linux/run.py |
Main entry point — orchestrates vision pipeline, decision engine, serial bridge, and web server |
linux/runnew.py |
Alternative entry point (same architecture, extended features) |
linux/src/detector.py |
YOLOv8n ONNX inference — detects people in camera frames |
linux/src/tracker.py |
Centroid-based multi-object tracker with speed estimation |
linux/src/state_machine.py |
Room Intelligence Engine — state transitions, comfort score, energy metrics |
linux/src/serial_bridge.py |
Serial communication bridge to Arduino (with mock fallback) |
linux/src/server.py |
FastAPI web server — dashboard HTML, WebSocket telemetry, REST APIs |
| File | Purpose |
|---|---|
arduino/src/Main/Main.ino |
Main MCU loop — serial commands, watchdog |
arduino/src/Main/HVACControl.cpp/h |
HVAC mode management (LED + relay control) |
arduino/src/Main/SerialComm.cpp/h |
Serial protocol handler (command parsing, telemetry output) |
arduino/src/Secondary/Secondary.ino |
IR blaster controller for Midea split AC |
arduino/src/Secondary/MideaIR.cpp/h |
Midea IR protocol encoder (38kHz carrier modulation) |
| Parameter | Source | Description |
|---|---|---|
| MCU Link | serial_bridge.get_telemetry()["mcu_connected"] |
Shows whether the Arduino Uno is physically connected via USB Serial. Green = connected, Red = mock mode |
| Uptime | time.time() - GlobalState.start_time |
How long the server has been running since launch (HH:MM:SS) |
| AUTO-OPTIMIZE ACTIVE | Static badge | Indicates the system is in autonomous control mode (not manual override) |
| Metric | Key | Source | How It's Calculated |
|---|---|---|---|
| Occupancy | occupancy |
len(boxes_dict) from tracker |
Count of currently tracked person bounding boxes |
| Room State | state |
RoomIntelligenceEngine.update() |
State machine output: EMPTY, IDLE, OCCUPIED, BUSY, HIGH_LOAD, or COOLING_BOOST |
| Comfort Score | comfort_score |
RoomIntelligenceEngine.update() |
50-100% — measures how well HVAC mode matches ideal mode for current occupancy |
| Target Temp | target_temp |
{0:26, 1:24, 2:22, 3:20, 4:18}[hvac_mode] |
Setpoint temperature mapped from HVAC mode |
| Estimated Power | power_kw |
RoomIntelligenceEngine.get_current_power_kw() |
Power draw for current mode: ECO=0.15kW, LOW=1.1kW, COMFORT=2.2kW, HIGH=3.2kW, BOOST=4.0kW |
| Energy Savings (₹) | savings_inr |
total_energy_saved_kwh × 8.0 |
Cumulative rupee savings vs. always-on baseline at ₹8/kWh tariff |
| CO₂ Avoided | co2_saved_kg |
total_energy_saved_kwh × 0.823 |
Cumulative CO₂ avoided using India's grid emission factor (0.823 kg CO₂/kWh) |
| Parameter | Source | Description |
|---|---|---|
| HVAC Policy | mode_names[hvac_mode] |
Current operating mode name: ECO, LOW_LOAD, COMFORT, HIGH_LOAD, BOOST |
| Confidence Score | Fixed 98% (occupied) / 100% (empty) | Confidence in the occupancy count accuracy |
| Explanation Text | engine.get_explanation(count) |
Human-readable rationale for the current HVAC decision |
| Manual Override Buttons | app.state.manual_override_mode |
Force ECO (mode 0), COMFORT (mode 2), or BOOST (mode 4) |
| Parameter | Key | How It's Calculated |
|---|---|---|
| TR Required | cooling_tr |
total_load_btu ÷ 12,000 |
| Space Load | space_load_btu |
volume_ft³ × 6 = 15,000 × 6 = 90,000 BTU/hr |
| People Load | people_load_btu |
occupancy × 500 BTU/hr per person |
| Plant Capacity | installed_capacity_tr |
Fixed at 12.0 TR (installed cooling capacity) |
| Plant Loading | plant_load_pct |
min(100, (cooling_tr ÷ installed_capacity_tr) × 100) |
| Grid CO₂ Impact | current_co2_kgph |
power_kw × 0.823 kg/kWh — real-time emission rate |
| Parameter | Source | Description |
|---|---|---|
| Left Zone | People with center_x < frame_width/3 |
Count of people in the left third of camera view |
| Centre Zone | People with frame_width/3 ≤ center_x < 2×frame_width/3 |
Count of people in the centre third |
| Right Zone | People with center_x ≥ 2×frame_width/3 |
Count of people in the right third |
| Recommended Action | build_airflow_recommendation() |
Plain-English instruction for where to direct airflow |
| Dataset | Y-Axis | Description |
|---|---|---|
| Occupancy (people) | Left axis (0-5+) | Blue line — tracked person count over time |
| HVAC Power (kW) | Right axis (0-5) | Yellow line — estimated power consumption |
| Parameter | Description |
|---|---|
| HVAC 1-4 Position | Pixel coordinates (x, y) of where each HVAC unit is located relative to camera frame |
| Calibration Status | Whether each HVAC unit has been mapped to camera coordinates |
| 2D Plan Map | Live canvas showing HVAC positions, person dots, and cooling beam targeting lines |
The total cooling load determines how much cooling capacity the room needs:
Total Load = Space Load + People Load
Space Load (BTU/hr) = Volume (ft³) × Load Factor
= 15,000 × 6
= 90,000 BTU/hr
People Load (BTU/hr) = Occupancy × Heat per Person
= N × 500 BTU/hr
Total Load (BTU/hr) = 90,000 + (N × 500)
Where:
15,000 ft³= auditorium volume (~425 m³)6 BTU/hr/ft³= envelope + equipment load factor500 BTU/hr/person= sensible + latent heat from a seated adult (ASHRAE standard)
TR Required = Total Load (BTU/hr) ÷ 12,000
Example: 5 people
= (90,000 + 2,500) ÷ 12,000
= 92,500 ÷ 12,000
= 7.71 TR
1 Ton of Refrigeration (TR) = 12,000 BTU/hr = the heat needed to melt 1 short ton of ice in 24 hours.
Plant Loading (%) = min(100, (TR Required ÷ Installed TR) × 100)
Example:
= min(100, (7.71 ÷ 12.0) × 100)
= 64.2%
This tells operators what fraction of the installed cooling infrastructure is being utilized.
Each zone (front-left, front-right) is calculated independently:
Zone Space Load (BTU/hr) = Zone Area (ft²) × 50
= 150 × 50
= 7,500 BTU/hr
Zone People Load (BTU/hr) = Zone People × 500
Zone Total (BTU/hr) = Zone Space + Zone People
Zone TR Required = Zone Total ÷ 12,000
Based on zone TR, each AC is set individually:
| Zone TR | AC Status | Temperature | Fan Speed | Power Draw |
|---|---|---|---|---|
| 0 (empty) | OFF | 26°C | OFF | 0.00 kW |
| < 0.5 TR | ON | 25°C | LOW | 0.605 kW (55% of 1.1 kW) |
| 0.5–0.9 TR | ON | 23°C | MEDIUM | 0.880 kW (80% of 1.1 kW) |
| ≥ 0.9 TR | ON | 21°C | HIGH | 1.100 kW (100%) |
Baseline Power = 3.2 kW (conventional always-on operation)
Current Power = mode_powers[hvac_mode] (0.15 to 4.0 kW)
Energy Saved per tick = (Baseline - Current) × (Δt / 3600) kWh
Cumulative Savings (₹) = Total kWh Saved × ₹8.0/kWh
CO₂ Avoided (kg) = Energy Saved (kWh) × 0.823 kg CO₂/kWh
Real-time CO₂ Rate = Current Power (kW) × 0.823 kg/kWh
The emission factor 0.823 kg CO₂/kWh is the CEA (Central Electricity Authority, India) weighted-average grid emission factor.
The tracker calculates per-person movement speed using Exponential Moving Average:
Raw Speed = ‖centroid_current − centroid_previous‖₂ (Euclidean distance in pixels)
Smoothed Speed = α × Raw Speed + (1 − α) × Previous Smoothed Speed
Where α = 0.3 (smoothing factor)
If HVAC mode < ideal mode for occupancy:
Comfort = max(50, 100 − (mode_gap × 20)) [under-cooling penalty]
If HVAC mode > ideal mode:
Comfort = 95 [over-cooling, energy waste]
If HVAC mode = ideal mode:
Comfort = 98 (occupied) or 100 (empty)
Activity Level:
"HIGH" → sum of all tracked speeds > 50 px/frame
"MEDIUM" → occupancy > 0 and speeds ≤ 50
"LOW" → occupancy = 0
┌────────────────────────────────────┐
│ COOLING_BOOST (4) │
│ Triggered by rapid entry │
│ (3+ people in 10s from EMPTY/IDLE)│
│ Times out after 90s │
└────────────────┬───────────────────┘
│ timeout
┌────────────────▼───────────────────┐
│ HIGH_LOAD (3) │
│ 6+ people │
└────────────────┬───────────────────┘
│ count drops
┌────────────────▼───────────────────┐
│ BUSY (3) │
│ 3-5 people, high activity (>30) │
└────────────────┬───────────────────┘
│ activity drops
┌────────────────▼───────────────────┐
│ OCCUPIED (2) │
│ 3-5 people low activity, or │
│ 1-2 people high activity (>25) │
└────────────────┬───────────────────┘
│ count drops
┌────────────────▼───────────────────┐
│ IDLE (1) │
│ 1-2 people, low activity │
│ │
└────────────────┬───────────────────┘
│ count = 0, no motion
┌────────────────▼───────────────────┐
│ EMPTY (0) │
│ No people, no motion │
└────────────────────────────────────┘
| Rule | Behavior | Purpose |
|---|---|---|
| Rapid Ramp-Up | If target state priority > current → transition immediately | Don't leave people sweating |
| Delayed Ramp-Down | If target state priority < current → wait 30 seconds | Prevents oscillation from brief exits |
| Boost Timeout | COOLING_BOOST → normal state after 90 seconds | Prevents indefinite overdrive |
| Room State | HVAC Mode | Mode ID | Target Temp | Power (kW) |
|---|---|---|---|---|
| EMPTY | ECO | 0 | 26°C | 0.15 |
| IDLE | LOW_LOAD | 1 | 24°C | 1.10 |
| OCCUPIED | COMFORT | 2 | 22°C | 2.20 |
| BUSY | HIGH_LOAD | 3 | 20°C | 3.20 |
| HIGH_LOAD | HIGH_LOAD | 3 | 20°C | 3.20 |
| COOLING_BOOST | BOOST | 4 | 18°C | 4.00 |
The system is a closed-loop pipeline where every component feeds into the next:
CAMERA FRAME
│
▼
[YOLOv8 Detector] ──▶ List of bounding boxes [x1,y1,x2,y2]
│
▼
[Centroid Tracker] ──▶ Persistent IDs + Bounding Boxes + Speeds
│
├──▶ [Zone Assignment] ──▶ front_zone_1 count, front_zone_2 count
│ │
│ ▼
│ [Zone Cooling Load] ──▶ BTU/hr per zone ──▶ TR per zone
│ │
│ ▼
│ [Dual-AC Optimizer] ──▶ AC1 commands (Serial to Arduino)
│ │ AC2 commands (UDP to Wi-Fi secondary)
│ │
│ ▼
│ [Serial Bridge] ──▶ Arduino Uno (relay, LEDs)
│ ◀── MCU state telemetry
│
├──▶ [State Machine] ──▶ Room State + HVAC Mode + Comfort Score
│ │
│ ▼
│ [Energy Calculator] ──▶ Power (kW), Savings (₹), CO₂ (kg)
│
├──▶ [3-Zone Distribution] ──▶ Left/Centre/Right people counts
│
├──▶ [Thermal Model] ──▶ Cooling TR, Plant Loading %, CO₂/hr
│
└──▶ [Dashboard Server] ──▶ WebSocket broadcast to browser
│
▼
[Browser UI] ──▶ Charts, Metrics, Video Feed, Calibration Map
- Detector → Tracker: Raw bounding boxes become persistent person IDs with speed
- Tracker → Zone Assignment: Person center-x determines which zone they're in
- Zone Assignment → AC Optimizer: Zone population drives per-zone cooling load calculation
- AC Optimizer → Serial Bridge: Translated to relay commands for Arduino Uno (AC1) and UDP packets for Wi-Fi controller (AC2)
- Tracker → State Machine: Person count + speed feed into temporal intelligence engine
- State Machine → Energy Calculator: HVAC mode determines power draw, savings vs baseline
- Everything → Dashboard: All metrics are compiled into a single WebSocket payload broadcast every 1 second
The room is split into two front zones (left half and right half of the camera frame):
┌─────────────────────────────────────────┐
│ CAMERA VIEW │
│ │
│ ┌──────────────┬──────────────┐ │
│ │ FRONT │ FRONT │ │
│ │ ZONE 1 │ ZONE 2 │ │
│ │ (AC1) │ (AC2) │ │
│ │ │ │ │
│ │ 👤 👤 │ 👤 │ │
│ │ │ │ │
│ └──────────────┴──────────────┘ │
│ boundary = frame_width/2 │
└─────────────────────────────────────────┘
- AC1 (Front Zone 1) is controlled via Serial → Arduino Uno relay
- AC2 (Front Zone 2) is controlled via Wi-Fi UDP → Secondary Arduino IR blaster
Each AC is independently set to the optimal temperature and fan speed based only on the people in its zone. If one zone is empty, that AC turns off — saving energy while the other zone still provides full comfort.
- Python 3.10+
- pip (Python package manager)
- Arduino IDE (for firmware upload)
- A webcam (Logitech C270 recommended)
git clone <repository-url>
cd ard18pip install -r requirements.txtThe key dependencies are:
fastapi+uvicorn— Web server and dashboardopencv-python— Video capture and image processingnumpy— Numerical operationsonnxruntime— YOLOv8 model inferencepyserial— Arduino serial communicationwebsockets— Real-time dashboard updates
The YOLOv8n ONNX model should be placed at:
linux/config/yolov8n.onnx
If missing, run the download script:
python linux/src/download_model.py- Open
arduino/src/Main/Main.inoin Arduino IDE - Select Arduino Uno board and correct COM port
- Upload
For the secondary AC controller:
- Open
arduino/src/Secondary/Secondary.ino - Upload to the secondary Arduino board
cd linux
python run.py --port COM3 --camera 0cd linux
python run.py --no-serial --camera 0If no webcam is available, the system automatically enters Virtual Room Simulator mode with animated person movement.
| Argument | Default | Description |
|---|---|---|
--port |
COM3 |
Serial port for Arduino Uno |
--camera |
0 |
Camera index (0 = try external USB first, then built-in) |
--no-serial |
false |
Run without physical Arduino |
--web-port |
8000 |
FastAPI dashboard port |
Open your browser to:
http://localhost:8000
| Method | Endpoint | Description |
|---|---|---|
GET |
/ |
Dashboard HTML page |
GET |
/api/video_feed |
MJPEG video stream |
GET |
/api/telemetry |
JSON snapshot of all current metrics |
WS |
/ws/telemetry |
WebSocket — real-time telemetry broadcast (1Hz) |
POST |
/api/override |
Manual HVAC mode override ({"mode": 0-4}) |
POST |
/api/camera |
Switch camera source ({"camera_index": 0 or 2}) |
POST |
/api/calibrate |
Capture HVAC position calibration ({"hvac_id": 1-4}) |
ard18/
├── README.md # This file
├── explanation.md # Brief explanation with demo points
├── requirements.txt # Python dependencies
│
├── arduino/
│ └── src/
│ ├── Main/ # Primary Arduino firmware
│ │ ├── Main.ino # Main loop (serial + watchdog)
│ │ ├── HVACControl.cpp/h # LED + relay mode control
│ │ └── SerialComm.cpp/h # Serial protocol handler
│ └── Secondary/ # Secondary AC controller
│ ├── Secondary.ino # IR blaster + receiver loop
│ ├── MideaIR.cpp/h # Midea AC IR protocol encoder
│ └── wifi_bridge.py # Wi-Fi UDP bridge script
│
├── linux/
│ ├── run.py # Main entry point
│ ├── runnew.py # Alternative entry point
│ ├── config/
│ │ └── yolov8n.onnx # YOLOv8n neural network model
│ └── src/
│ ├── detector.py # YOLOv8 ONNX person detection
│ ├── tracker.py # Centroid multi-object tracker
│ ├── state_machine.py # Room Intelligence Engine
│ ├── serial_bridge.py # Arduino serial bridge
│ └── server.py # FastAPI dashboard + WebSocket
│
├── calibration/ # HVAC position calibration data
│ ├── calibration_coords.json # Saved (x,y) per HVAC unit
│ └── hvac_*_calib.jpg # Annotated calibration snapshots
│
└── scratch/ # Development utility scripts
| Problem | Solution |
|---|---|
| "Camera not detected" | System auto-switches to simulator mode. Check USB webcam connection |
| Dashboard shows "MCU: Mock Link" | Arduino not connected or wrong COM port. Use --no-serial for demo |
| Port 8000 busy | System auto-increments port. Check console for actual URL |
| All metrics frozen at zero | WebSocket /ws/telemetry should be connected. Check browser console |
| HVAC mode oscillating rapidly | Debounce is set to 30s. If still oscillating, increase debounce_down_seconds |
This project was built for the Arduino HVAC Hackathon competition. See repository license for terms.