Issue overview
I'm running an OpenStudio-resources regression test that has:
- A VRF Terminal (regular) in most zones
- A VRF Terminal on the main branch of an AirLoopHVAC
- A VRF Terminal on the OA Intake of an AirLoopHVAC:OutdoorAirSystem, which is the one given the warning
- Note: this VRF TU has a supply fan assigned... I know the IDD seems to imply that it shouldn't...
I'm running the file with the Chicago TMY. The OpenStudio test is at NatLabRockies/OpenStudio-resources#137 and I added the IDF to the EnergyPlusDevSupport
** Warning ** AirConditioner:VariableRefrigerantFlow "AIR CONDITIONER VARIABLE REFRIGERANT FLOW 1".
** ~~~ ** ...InitVRF: VRF Heat Pump Min/Max Operating Temperature in Heating Mode Limits have been exceeded and VRF system is disabled.
** ~~~ ** ... Outdoor Unit Inlet Air Temperature = -20.149
** ~~~ ** ... Heating Minimum Outdoor Unit Inlet Temperature = -19.999
** ~~~ ** ... Heating Maximum Outdoor Unit Inlet Temperature = 30.000
** ~~~ ** ... Check VRF Heat Pump Min/Max Outdoor Temperature in Heating Mode limits.
** ~~~ ** Environment=RUN PERIOD 1, at Simulation time=01/07 03:00 - 03:15
** Warning ** ZoneHVAC:TerminalUnit:VariableRefrigerantFlow "VRF TERMINAL ON OA SYSTEM"
** ~~~ ** Terminal unit part-load ratio calculation failed: PLR limits of 0 to 1 exceeded
** ~~~ ** Please fill out a bug report and forward to the EnergyPlus support group.
** ~~~ ** Environment=RUN PERIOD 1, at Simulation time=07/19 11:45 - 12:00
Details
Some additional details for this issue (if relevant):
- Platform (Operating system, version): all
- Version of EnergyPlus (if using an intermediate build, include SHA): v9.5.0-IOFreeze
Checklist
Add to this list or remove from it as applicable. This is a simple templated set of guidelines.
- Defect file added (list location of defect file here): https://github.com/NREL/EnergyPlusDevSupport/blob/6da32a25c7ee3a7d6e2c237ac483acfe0a2b6e4e/DefectFiles/8000s/8640/vrf_airloophvac_rb.idf#L2754-L2784
- Ticket added to Pivotal for defect (development team task)
- Pull request created (the pull request will have additional tasks related to reviewing changes that fix this defect)