Additional Terminal Unit Sizing Issues #6481
Description
Issue overview
Followup terminal unit sizing issue from #6338.
-
In
SimAirServingZones::UpdateSysSizing, DesHeatCoilInTempTUis set for heating zones only usingGetHeatingSATempForSizing(similar for humrat) here. In Fix VAV min flow frac > 1.0 and a bunch of termunitsizing issues related to multiple airloops #6338, for consistency with other blocks inUpdateSysSizing, I added a loop here over cooled zones for completeness, show here. But that caused large changes in reheat coil sizing across many files - maybe these are OK, but too much to review at this point, so the new block over cooled zones was removed. -
Review diffs from system sizing refactor System sizing adjustments for Std 61.2 VRP - fix and refactor #6372 and fix here if needed.
-
Review diffs from new coil sizing report New Coil Sizing Reports #6454 and possibly reinstate or modify the lines that were reverted here which, BTW, were suspected of causing diffs but nothing changed after this commit. Also, see various comments from @rraustad in New Coil Sizing Reports #6454 .
@EnergyArchmage addressed this in 75fdccb -
Try to resolve performance hit introduced in System sizing adjustments for Std 61.2 VRP - fix and refactor #6372 Here are the timing results from System sizing adjustments for Std 61.2 VRP - fix and refactor #6372 and the prior merge which was Automatic Import of Shading from a CSV File #6388
PR6372 timing results.pdf
PR6388 timing results.pdf
Addressed in add trap to not process population concurrence unless VRP present #6489 -
PR6481 initially caused a bunch of new errr messages about table units conversions
** Warning ** Unable to find a unit conversion from Coil Entering Air Humidity Ratio at Ideal Loads Peak [kg-H2O/kg-DryAir] into IP units
+ ** ~~~ ** Applying default conversion factor of 1.0
+ ** Warning ** Unable to find a unit conversion from Outdoor Air Humidity Ratio at Ideal Loads Peak [kg-H2O/kg-DryAir] into IP units
+ ** ~~~ ** Applying default conversion factor of 1.0
+ ** Warning ** Unable to find a unit conversion from Zone Air Humidity Ratio at Ideal Loads Peak [kg-H2O/kg-DryAir] into IP units
+ ** ~~~ ** Applying default conversion factor of 1.0
+ ** Warning ** Unable to find a unit conversion from Plant Design Fluid Temperature Difference [Delta C] into IP units
These have been addressed in bb00e38 by switching to existing units strings, e.g. KGWATER/KGDRYAIR, but we might prefer to add some new units strings instead.
- Other errors from New Coil Sizing Reports #6454
5ZoneDDCycOnAny and many others
+ ** Severe ** MyPlantSizingIndex: Could not find HOT WATER LOOP in Sizing:Plant objects.
+ ** ~~~ ** ...reference Component Type="hot water coil", Name="SPACE1-1 ZONE COIL".
UnitarySystem_WaterCoils_wMultiSpeedFan
+ ** Warning ** In calculating the design coil UA for Coil:Cooling:Water CW COOLING COIL
+ ** ~~~ ** no apparatus dew-point can be found for the initial entering and leaving conditions;
+ ** ~~~ ** the coil outlet design conditions will be changed to correct the problem.
VSHeatPumpWaterHeater
+ ** Warning ** WetBulb not converged after 101 iterations(PsyTwbFnTdbWPb)
+ ** ~~~ ** Routine=ReportCoilSelection::doFinalProcessingOfCoilData,
-
Coil locations are not being found now
-
Need unit tests for both Std 62 and coil sizing report.
Details
Some additional details for this issue (if relevant):
- Platform (Operating system, version)
- Version of EnergyPlus (if using an intermediate build, include SHA)
- Unmethours link or helpdesk ticket number
Checklist
Add to this list or remove from it as applicable. This is a simple templated set of guidelines.
- Defect file added (list location of defect file here)
- Ticket added to Pivotal for defect (development team task)
- Pull request created (the pull request will have additional tasks related to reviewing changes that fix this defect)