DOATToUnitVentilator node connection errors #6273
Copy link
Copy link
Closed
Labels
PriorityHighThis defect or feature has been declared high priorityThis defect or feature has been declared high priority
Milestone
Description
Issue overview
Not sure when this slipped in, but DOATToUnitVentilator is now throwing node connection errors. Checked all of the DOATo* files and the others are OK.
** Severe ** Node Connection Error, Node="ZONE1UNITVENTOAMIXEROUTLETNODE", The same node appears as a non-parent Inlet node more than once.
** ~~~ ** Reference Object=ZONEHVAC:UNITVENTILATOR-OA MIXER, Name=TU1
** ~~~ ** Reference Object=FAN:CONSTANTVOLUME, Name=ZONE1UNITVENTFAN
** Severe ** Node Connection Error, Node="ZONE2UNITVENTOAMIXEROUTLETNODE", The same node appears as a non-parent Inlet node more than once.
** ~~~ ** Reference Object=FAN:CONSTANTVOLUME, Name=ZONE2UNITVENTFAN
** ~~~ ** Reference Object=ZONEHVAC:UNITVENTILATOR-OA MIXER, Name=TU2
** Severe ** Node Connection Error, Node="ZONE3UNITVENTOAMIXEROUTLETNODE", The same node appears as a non-parent Inlet node more than once.
** ~~~ ** Reference Object=FAN:CONSTANTVOLUME, Name=ZONE3UNITVENTFAN
** ~~~ ** Reference Object=ZONEHVAC:UNITVENTILATOR-OA MIXER, Name=TU3
** Severe ** Node Connection Error, Node="ZONE4UNITVENTAIRINLETNODE", The same node appears as a non-parent Inlet node more than once.
** ~~~ ** Reference Object=FAN:CONSTANTVOLUME, Name=ZONE4UNITVENTFAN
** ~~~ ** Reference Object=ZONEHVAC:UNITVENTILATOR-OA MIXER, Name=TU4
** Severe ** Node Connection Error, Node="ZONE5UNITVENTAIRINLETNODE", The same node appears as a non-parent Inlet node more than once.
** ~~~ ** Reference Object=FAN:CONSTANTVOLUME, Name=ZONE5UNITVENTFAN
** ~~~ ** Reference Object=ZONEHVAC:UNITVENTILATOR-OA MIXER, Name=TU5
************* There were 5 node connection errors noted.
Details
Some additional details for this issue (if relevant):
- Version of EnergyPlus Version 8.8.0-ddaa5689de
Checklist
Add to this list or remove from it as applicable. This is a simple templated set of guidelines.
- Defect file testfiles\DOATToUnitVentilator.idf
- Ticket added to Pivotal for defect (development team task)
- Pull request created (the pull request will have additional tasks related to reviewing changes that fix this defect)