Skip to content

Suspect zone hvac heating coil sizing with DOAS mixer #6243

@mjwitte

Description

@mjwitte

Issue overview

While testing changes for #6223, I tried changing the OA spec to be 10% of the original and then compared the eio outputs expecting the DOAS components to all be 10% of the original That much works as expected. I also expected no change in the zone HVAC system sizing.

  1. For the fan coil test file, the fan coil components were all the same size in zones 1-4, as expected. But in zone 5, the fan coil heating coil got smaller.

  2. For the PTHP test file, all five of the supp heating coils got smaller.

In both cases, I made sure that the Sizing:Zone "account for DOAS" was set to no.

Details

Some additional details for this issue (if relevant):

  • Platform (Operating system, version)
  • Version of EnergyPlus v8.7.0 fdb3cf2

Checklist

Add to this list or remove from it as applicable. This is a simple templated set of guidelines.

  • Defect file added (list location of defect file here)
  • Ticket added to Pivotal for defect (development team task)
  • Pull request created (the pull request will have additional tasks related to reviewing changes that fix this defect)

Metadata

Metadata

Assignees

Labels

DefectIncludes code to repair a defect in EnergyPlusPriorityHighThis defect or feature has been declared high priority

Type

No type

Projects

No projects

Milestone

No milestone

Relationships

None yet

Development

No branches or pull requests

Issue actions