Suspect zone hvac heating coil sizing with DOAS mixer #6243
Copy link
Copy link
Open
Labels
DefectIncludes code to repair a defect in EnergyPlusIncludes code to repair a defect in EnergyPlusPriorityHighThis defect or feature has been declared high priorityThis defect or feature has been declared high priority
Description
Issue overview
While testing changes for #6223, I tried changing the OA spec to be 10% of the original and then compared the eio outputs expecting the DOAS components to all be 10% of the original That much works as expected. I also expected no change in the zone HVAC system sizing.
-
For the fan coil test file, the fan coil components were all the same size in zones 1-4, as expected. But in zone 5, the fan coil heating coil got smaller.
-
For the PTHP test file, all five of the supp heating coils got smaller.
In both cases, I made sure that the Sizing:Zone "account for DOAS" was set to no.
Details
Some additional details for this issue (if relevant):
- Platform (Operating system, version)
- Version of EnergyPlus v8.7.0 fdb3cf2
Checklist
Add to this list or remove from it as applicable. This is a simple templated set of guidelines.
- Defect file added (list location of defect file here)
- Ticket added to Pivotal for defect (development team task)
- Pull request created (the pull request will have additional tasks related to reviewing changes that fix this defect)
Reactions are currently unavailable
Metadata
Metadata
Assignees
Labels
DefectIncludes code to repair a defect in EnergyPlusIncludes code to repair a defect in EnergyPlusPriorityHighThis defect or feature has been declared high priorityThis defect or feature has been declared high priority