PTAC heating coil undersized for ventilation load when zone design heating load is zero #6028
Copy link
Copy link
Closed
Labels
PriorityLowThis defect or feature has been declared low priorityThis defect or feature has been declared low prioritySeverityHighThis defect is high severity, generally indicating a hard crash without a workaroundThis defect is high severity, generally indicating a hard crash without a workaround
Milestone
Description
Issue overview
User file has PTACs with hot water heating coils. PTACs provide ventilation air. For zones with a zero design zone heating load, the PTAC heating coil is undersized and cannot temper the ventilation load. Adding a small negative other equipment load to those zones in order to force a non-zero design heating load fixes the coil sizing. Unit 116 and Unit 206 show the problem.
Details
Some additional details for this issue (if relevant):
- Platform (Operating system, version)
- Version of EnergyPlus 8.6.0
- Helpdesk ticket 11551
Checklist
Add to this list or remove from it as applicable. This is a simple templated set of guidelines.
- Defect file added EnergyPlusDevSupport\DefectFiles
- Ticket added to Pivotal for defect (development team task)
- Pull request created (the pull request will have additional tasks related to reviewing changes that fix this defect)
Reactions are currently unavailable
Metadata
Metadata
Assignees
Labels
PriorityLowThis defect or feature has been declared low priorityThis defect or feature has been declared low prioritySeverityHighThis defect is high severity, generally indicating a hard crash without a workaroundThis defect is high severity, generally indicating a hard crash without a workaround