Skip to content

PTAC heating coil undersized for ventilation load when zone design heating load is zero #6028

@mjwitte

Description

@mjwitte

Issue overview

User file has PTACs with hot water heating coils. PTACs provide ventilation air. For zones with a zero design zone heating load, the PTAC heating coil is undersized and cannot temper the ventilation load. Adding a small negative other equipment load to those zones in order to force a non-zero design heating load fixes the coil sizing. Unit 116 and Unit 206 show the problem.

Details

Some additional details for this issue (if relevant):

  • Platform (Operating system, version)
  • Version of EnergyPlus 8.6.0
  • Helpdesk ticket 11551

Checklist

Add to this list or remove from it as applicable. This is a simple templated set of guidelines.

  • Defect file added EnergyPlusDevSupport\DefectFiles
  • Ticket added to Pivotal for defect (development team task)
  • Pull request created (the pull request will have additional tasks related to reviewing changes that fix this defect)